The ICAM IFT-4 and IFT-6 by Xtralis are aspirating smoke detection systems with an alarm sensitivity range from 0.001% to 20% obscuration/m (0.0003% to 6.10% obscuration/ft). These detectors are classified as Very Early Warning Smoke Detectors that can reliably detect fire at an early stage, and low to high concentrations of smoke over an area of 2,000 m2 (21,500 sq. ft.). The detectors are configurable for a variety of environments. Addressability provides more detail into fire location, enabling faster response.Model Numbers: IFT-4, IFT-6
FEATURES
- 4 and 6 zones
- Large bore 4- and 6-pipe air sampling
- 0.001% to 20% obscuration/m (0.0003% to 6.10% obscuration/ft)
- 4 Alarms - Alert, Action, Fire 1, Fire 2
- 4 x 100 m (4 x 328 ft) and 6 x 100 m (6 x 328 ft.) sampling pipe
- Enhanced performance aspirator
- Ethernet TCP/IP
- RS232 and RS485 Modbus
- Up to 16 additional relay outputs available
- Optional 4 to 20 mA analog outputs
- Area coverage of up to 2000 m2 (21,500 sq. ft.)
APPLICATIONS
- Telecom and IT facilities
- Heavy industrial environments such as chemical plants, factories, warehouses and mining facilities
- Areas of more than 2,000 square meters, especially when the area is not wide open, such as a document storage facility where you can't see past the shelving
CERTIFICATIONS
- FM
- UL
- VdS
- CFE
- CE-EMC
- LVD
- CPD
- CSFM
- EN54-20













Introduction

Product Overview