cb200e Gas Release Control Panel

Key Features

  • Co-incidence zone operation
  • Auxiliary zone
  • Manual release zone
  • Emergency abort feature
  • 3 configurable alarm circuits
  • Aux fire and fault relays
  • Auto/Manual user selection
  • Discharge delay up to 60 seconds
  • Instant or timed release operation on manual release operation
  • One man test mode
  • Earth fault enable/ disable
  • Full zone isolate functions

Introduction

The CB200e is a single area gaseous extinguishant panel.

Zones 1 and 2 are configured for double knock, time delayed  activation of the actuator output. 

Zone 3 is primarily for manual call points and does not provide any form of control over the actuator circuits.

The emergency abort is a fault monitored, latching input which when  active will:

  1. Raise a steady abort indication
  2. Operate the buzzer
  3. Prevent the actuator circuit from operating.  


The inhibit condition will remain latched until the panel is reset.

The manual release zone will:

  1. When set to instant manual release activation, operate alarm   circuit 3 continuously and operate the actuator circuit. 
  2. When set to timed manual release activation, operate alarm circuit  3 in pulsed mode and start the actuator delay timer. 

Alarm circuits 1 and 2 will:

  1. Operate continuously for a fire condition on any zone 1, 2 or aux zone until silenced. 
  2. Operate continuously on activation of the evacuate button on the  panel display until the evacuate button is pressed again. 
  3. Operate on any fire condition on zones 1, 2 or aux zone in one  man test mode, auto silencing after each fire test. 
  4. Operate intermittently while the pre-discharge timer is running,  changing to continuous when the actuator circuit activates. The  silence alarm switch will be automatically disabled during the pre-discharge delay to prevent silencing of the sounders. 

Pre discharge time delay is started by zone 1 and 2 double knock fire in automatic status or manual release operation when configured to timed manual release operation. On time out the actuator circuit operates and changes the mode of alarm circuit 3 from pulsed to continuous operation. 
Time delay configuration. The operation of the actuator circuit and alarm circuit 3 can be delayed from zero to 60 seconds, in 10-second steps.

Specification

Mains supply: 230VAC +10% -15% at 50 Hz

Maximum field equipment load:  800mA

Auxiliary 24VDC output: 250mA

Mains failed current consumption: 40mA @24VDC

Integral battery charger output: 500mA @27.5VDC

Common fire relay: Volt-free contacts - 1A, 30V DC max.

Common fault relay: Not available

1st stage alarm circuit output: 2at 500mA each @28VDC

2nd stage [actuator operated] alarm output: 1at 500mA each @28VDC

Detection zones & manual release zone: Max number of devices per zone- 32

Inhibit input and Auto/manual input: Max number of devices per input- 1

Actuator outputs: 1 at 500mA @28VDC

Battery size: 2 x 12V 2.1AH sealed lead acid

Weight (excluding batteries): 2.4 kg


 
Banner

We have 11 guests online
  • An Image Slideshow
  • An Image Slideshow
  • An Image Slideshow
  • An Image Slideshow
  • An Image Slideshow
  • An Image Slideshow










Copyright © 2007-2011 Hong Thuyen Trading & Service Co., Ltd. All rights reserved.
290 Chu Van An Street (back door)., 26th Ward, Binh Thanh District, Ho Chi Minh City, Vietnam
Developed by Thiết Kế Website Đẹp! - Powered by Top 10 Google Ranking!