MX300 GR 4 Zones Fire Alarm & Single Hazard Agent Release Control Panel for Fire Suppression Systems
Features- Tested & Approved to British Standard EN54 Part 2 & Part 4 : 1998
- Tested & Approved to Singapore Standard CP10 : 2005
- Selectable Cross Zones or Single Zone Release
- Built in additional 4 Alarm Zones • 2 Digit 7-Segment Count Down Timer with Selectable Time Delay 0 to 90 seconds
- Power Supply meets EN 60950, UL 1012, and UL 1950 Safety Standards
- Separate input for “Abort” and “Manual Release” Signals
- Status indication for Discharge Pressure Switch
- Simultaneous illumination of “Gas Discharge Warning Sign”
- Standard Transient Surge Protection • Selectable out put Dry Contact or 24 VDC
General
Description MX300 GR is designed for use with Fire Extinguishing Systems such as Stat-X, FM-200 (HFC-227ea), Inert Gas, CO2 , Novec 1230, etc. Panel comes with 2 Initiating Zones that is select-able for Cross Zones (both Zones in alarm before the agent can be release) or Single Zone (any one zone in alarm for agent release). Beside the 2 Initiating Zones, MX300 GR also comes with 4 build in Alarm Zones. The additional features can be used to wired to High Sensitivity Smoke Detection Systems to give early warning without involving the Suppression System Initiating Zones. These 4 build in Alarm Zones can also be used for standard fire alarm purpose, wiring to call points and detectors.
Specification
- Cabinet Dimensions: 410 x 375 x 150mm
- Initiating / Detection Circuits: 2 x Class B
- Fire Alarm Detection Circuits: 4 x Class B
- Countdown Timer Display: 2 x 7 Segment LED Digits
- Countdown Time Delay Setting: 0 to 90 seconds (10 sec increment)
- First Stage Alarm Output: 3 x NO/NC Relay, 5 x 24VDC Output
- Second Stage Alarm Output: 2 x NO/NC Relay, 2 x Releasing Circuits (1A @ 24VDC, 2A total)
- Alarm Relay Contact Output: 1 x NO/NC
- Fault Relay Contact Output: 1 x NO/NC
- Independent Isolate Switch for input & output: 2 x Initiating / Detection Zones; 4 x Alarm Zones; 1 x Abort Switch; 1 x Manual Release; 1 x Solenoid Release
- AC Input: 110VAC or 220VAC
- Standby Battery: 2 x 7AH 12VDC Sealed Lead Acid (fit inside cabinet)













Introduction

Product Overview