Hong Thuyen Trading Service Co.,Ltd - 290 Chu Van An Street (back door)., 26th Ward, Binh Thanh District, Ho Chi Minh City, Vietnam

Hong Thuyen Trading Service Co.,Ltd

Home Fire Alarm and Detection Systems Agent Release Control System Pyrogard Gas Control Release Panel - MX300 GR

Pyrogard Gas Control Release Panel - MX300 GR


MX300 GR 4 Zones Fire Alarm &  Single Hazard Agent  Release Control Panel for Fire Suppression Systems

Features
  • Tested & Approved to British Standard EN54 Part 2 & Part 4 : 1998
  • Tested & Approved to Singapore Standard CP10 : 2005
  • Selectable Cross Zones or Single Zone Release
  • Built in additional 4 Alarm Zones • 2 Digit 7-Segment Count Down Timer with Selectable Time Delay 0 to 90 seconds
  • Power Supply meets EN 60950, UL 1012, and UL 1950 Safety Standards
  • Separate input for “Abort” and “Manual Release” Signals
  • Status indication for Discharge Pressure Switch
  • Simultaneous illumination of “Gas Discharge Warning Sign”
  • Standard Transient Surge Protection • Selectable out put Dry Contact or 24 VDC

General


Description MX300 GR is designed for use with Fire Extinguishing Systems such as  Stat-X, FM-200 (HFC-227ea), Inert Gas, CO2 , Novec 1230, etc.  Panel comes with 2 Initiating Zones that is select-able for Cross Zones (both Zones in alarm before the agent can be release) or Single Zone (any one zone in alarm for agent release). Beside the 2 Initiating Zones, MX300 GR also comes with 4 build in Alarm Zones. The additional features can be used to wired to High Sensitivity Smoke Detection Systems to give early warning without involving the Suppression System Initiating Zones. These 4 build in Alarm Zones can also be used for standard fire alarm purpose, wiring to call points and detectors.

Specification

  • Cabinet Dimensions: 410 x 375 x 150mm
  • Initiating / Detection Circuits: 2 x Class B
  • Fire Alarm Detection Circuits: 4 x Class B
  • Countdown Timer Display: 2 x 7 Segment LED Digits
  • Countdown Time Delay Setting: 0 to 90 seconds (10 sec increment)
  • First Stage Alarm Output: 3 x NO/NC Relay, 5 x 24VDC Output
  • Second Stage Alarm Output: 2 x NO/NC Relay, 2 x Releasing Circuits (1A @ 24VDC, 2A total)
  • Alarm Relay Contact Output: 1 x NO/NC
  • Fault Relay Contact Output: 1 x NO/NC
  • Independent Isolate Switch for input & output: 2 x Initiating / Detection Zones; 4 x Alarm Zones; 1 x Abort Switch; 1 x Manual Release; 1 x Solenoid Release  
  • AC Input: 110VAC or 220VAC
  • Standby Battery: 2 x 7AH 12VDC Sealed Lead Acid (fit inside cabinet)



 


 
Banner

We have 20 guests online
  • An Image Slideshow
  • An Image Slideshow
  • An Image Slideshow
  • An Image Slideshow
  • An Image Slideshow
  • An Image Slideshow










Copyright © 2007-2011 Hong Thuyen Trading & Service Co., Ltd. All rights reserved.
290 Chu Van An Street (back door)., 26th Ward, Binh Thanh District, Ho Chi Minh City, Vietnam
Developed by Thiết Kế Website Đẹp! - Powered by Top 10 Google Ranking!